Generator set

100 kVA – diesel

Manufacturer: Metal-Technik

Metal Technik vM unit

ATM-100-BL generator set – 100 kVA – diesel

Metal-Technik diesel-powered generators are devices used to generate electricity in places where there is no permanent access to the mains supply or in the event of a power cut.

They are characterised by:

  • High performance and durability – diesel engines can withstand heavy use and operate for many hours.
  • Lower fuel consumption compared to petrol engines of the same power output, which translates into savings during prolonged operation.
  • With high power output and stable voltage, they are suitable for powering industrial equipment, professional tools, emergency systems, construction sites and public facilities.
  • Applications across various sectors – from construction and industry, through to medicine and IT, and on to agriculture and households.
  • Fitted with safety and automation systems – including an automatic transfer switch (ATS) in the event of a power cut, and overload protection.

Diesel fuel offers better efficiency and a longer engine service life, making diesel generators the ideal choice where high power output and long-term reliability are required.

ATM-100-BL generator set – 100 kVA – diesel

Metal-Technik diesel-powered generators are devices used to generate electricity in places where there is no permanent access to the mains supply or in the event of a power cut.

They are characterised by:

  • High performance and durability – diesel engines can withstand heavy use and operate for many hours.
  • Lower fuel consumption compared to petrol engines of the same power output, which translates into savings during prolonged operation.
  • With high power output and stable voltage, they are suitable for powering industrial equipment, professional tools, emergency systems, construction sites and public facilities.
  • Applications across various sectors – from construction and industry, through to medicine and IT, and on to agriculture and households.
  • Fitted with safety and automation systems – including an automatic transfer switch (ATS) in the event of a power cut, and overload protection.

Diesel fuel offers better efficiency and a longer engine service life, making diesel generators the ideal choice where high power output and long-term reliability are required.

show more of the description

Specifications of the ATM-100-BL generator set – 100 kVA – diesel

Model100 kVA – diesel
EngineBaudouin - 4M10G110/5
GeneratorLeroy Sommer – TAL 044 D
ESP maximum power [kVA/kW]107,0 / 86,0
PRP rated power [kVA/kW]98,0 / 78,0
Rated current [A]141,0
Frequency [Hz]50
Rated voltage [V]230/400
Power factor [cos]0,8
Exhaust emissionszero-emission
Fuel typeDiesel
Fuel tank capacity [l]255
Fuel consumption for the 50% [l/h]7,7
Fuel consumption for the 75% [l/h]11,1
Fuel consumption for the 80% [l/h]-
Fuel consumption for the 100% [l/h]15,1
Fuel consumption for the 110% [l/h]16,67
Range for the 80% load [h]21,0
Runtime for a 100% load [h]15,6
Weight of the unit without fuel [kg]1370
Dimensions L x W x H [mm]2400 x 1170 x 1670
Lwa’s guaranteed sound power [dBA]94
Sound pressure at 7 m LPa [dBA]68.8 ± 1

Comments

Definitions:
Rated power (PRP – Prime Rated Power) in accordance with ISO 8528-1:2018:
The maximum power that a generator set is capable of producing under variable load for an unlimited number of hours per year, under the agreed operating conditions, whilst adhering to the maintenance schedules and procedures specified by the manufacturer. Over a 24-hour period, the average load factor must not exceed 70%. At this power output, an overload of 10% is permitted for 1 hour within any 12-hour period.
Maximum ESP (Emergency Standby Power) output in accordance with ISO 8528-1:2018: The maximum power available during a variable electrical power sequence, under specified operating conditions, which the generator set is capable of supplying in the event of a loss of the main power supply or under test conditions for a maximum of 200 operating hours per year, provided that the maintenance intervals and procedures specified by the manufacturer are adhered to. Over a 24-hour period, the average load factor is 70%. Overloading at this power level is not permitted.

Standards and Directives:
Machinery Directive 2006/42/EC
Low Voltage Directive 2014/35/EU
Electromagnetic Compatibility Directive 2014/30/EU
Noise Directive 2000/14/EC

Standard equipment

  • ComAp IL-AMF25 controller
  • Brushless generator
  • Digital AVR
  • Schneider generator main switch
  • Reinforced, damage-resistant frame
  • Circuit-breaker tripping coil
  • Transformer battery charger
  • Engine block heater
  • Rapid load acceptance
  • Electronic speed controller
  • Direct-injection fuel system
  • 240-litre frame tank with a retention sump and sound-absorbing insulation
  • Electronic fuel gauge
  • Flexible anti-vibration mounts
  • Generator insulation class H
  • IP23 protection rating for the generator
  • Digital voltage regulation: +/-0.25%
  • 4 lifting points with slings
  • Extended runners to facilitate attachment to the ground

Optional equipment

  • Type-approved trailer for mobile units
  • SZR cabinet (automatic reserve switch-over)
  • Remote start and operation via a PC or GSM modem
  • GPS tracking
  • Additional external fuel tanks
  • The refuelling system located within the unit
  • Manual oil drain pump
  • Electronic oil drain pump
  • Leak detector in the retention chamber
  • Manual fuel drain pump
  • Electronic fuel drain pump (12V)
  • Additionally, a heated engine block
  • Heated electronic control unit for the power unit

Downloads

No files to download

All Generators

Metal Technik vM unit

Enquire about a generator

Choose how you’d like to get in touch
Breakdown of Metal Technik regions